Air & water Cooled Chillers

TT-14500

This water chiller features 14kw cooling & a 6kw heater with flow control – for use at water temperatures from +10ºC up to +40ºC and ambient temperatures up to +45ºC.

  • Compressor switches on and off automatically to maintain set temperature - circulation pump runs continuously
  • Self-optimising microprocessor controller with digital display of set and actual temperature
  • Seal-less pump made of corrosion free bronze
  • Electronic control of compressor operating time for extended working life
  • All components in contact with water are stainless steel or bronze
  • Anti-freeze thermostat prevents freezing
  • Automatic or manual refill
  • Automatic level control with pre-warning at low water level
  • Audible alarm in case of failure
Specifications

There are 2 different models available:
TT-14500 H Air-cooled unit with heating element
TT-14500 WK Water-cooled unit
 

Model TT-14500 H TT-14500 WK
Cooling Capacity:    
Circulating Water +10ºC up to +40ºC    +10ºC up to +40ºC
Air Temperature +2ºC up to +45ºC +2ºC up to +45ºC
Heating: 6kw 6kw
Contents Water: approx. 50 Litres approx. 50 Litres
Refrigeration Agent: R-134a R-134a
Air Volume:  2'850 m3/h  no fan
Power Consumption:   approx. 11,3 kW   approx. 5,0 kW 
Connections:       
TO/FROM mould  3/4" female thread  3/4" female thread 
Auto. water refill  3/8" female thread  3/8" female thread 
Cooling water IN/OUT    3/4" female thread 
Dimensions L x W x H:  950 x 660 x 1'300 mm, incl. castors  
Noise level:(in 3 m)  68 dBA  68 dBA 
Weight:    
Colour:  or stainless steel case   not varnished 
Pump Capacity:      max 8.5 bar  max 75 l/min
Compresssor:    5kW  
Temperature Control:    Self-optimising microprocessor controller with digital display 
of set and actual temperatures
Condenser:  Air cooled, air inlet located on the front, blow out located on the side/rear  
Model TT-14000 WK is water cooled and needs at least 1,5 bar water pressure: 
with cooling water(approx. 30ºC): approx. 20-40 l/min. cooling water consumption
with tap water (approx. 10 - 15ºC): approx. 20-40 l/min. cooling water consumption

 

Safety Devices
  • Level control provides auto dry run protection
  • Separate mechanical safety thermostat for maximum and minimum temperature
  • Temperature limiter installed in the controller
  • Main switch, automatic cutouts, transformer and main protection switch
  • Audible and visual alarm in case of  failure
Enquire Now

Need help or advice on our products? Enquire Now

/Content/Images/news/Chemical.jpg

Latest News

Chemical

In 2018 Tool-Temp installed two TT430 Y units to a chemical company. These units were produced for the customer and are now listed as a machine in our product range. We flew the customer out to our head office in Switzerland to meet with the person in charge of the project, once they had all the requirements the machines went through to production. The units are equipped with three independent heat exchangers. The three-circuit cooling system makes it possible to work with oil below zero degrees. The installed self-optimizing temperature controller MP-988 works with three temperature probe inlets. The reference temperature for the regulation can be the temperature of the product inside the vessel or the oil temperature in the tank of the unit. To avoid any damage of the jacket, the pump pressure can be adjusted to the specifications of the vessel/reactor. The pump revolutions per minute can be adjusted very easily using the frequency inverter. As well as many other features.

Read Article More News